annotations:
current: "{{ $value | humanize }}kVA"
- alert: site temperature
- expr: min(rPDU2SensorTempHumidityStatusTempC{site="amsterdam"}) / 10 < 18 or min(rPDU2SensorTempHumidityStatusTempC{site="amsterdam"}) / 10 > 26
+ expr: min(rPDU2SensorTempHumidityStatusTempC{site="amsterdam"}) / 10 < 15 or min(rPDU2SensorTempHumidityStatusTempC{site="amsterdam"}) / 10 > 32
for: 6m
labels:
alertgroup: "amsterdam"
annotations:
temperature: "{{ $value | humanize }}C"
- alert: site humidity
- expr: max(rPDU2SensorTempHumidityStatusRelativeHumidity{site="amsterdam"}) / 100 < 0.25 or max(rPDU2SensorTempHumidityStatusRelativeHumidity{site="amsterdam"}) / 100 > 0.65
+ expr: max(rPDU2SensorTempHumidityStatusRelativeHumidity{site="amsterdam"}) / 100 < 0.08 or max(rPDU2SensorTempHumidityStatusRelativeHumidity{site="amsterdam"}) / 100 > 0.8
for: 6m
labels:
alertgroup: "amsterdam"
for: 10m
labels:
alertgroup: "prometheus"
+ - alert: node exporter text file scrape error
+ expr: node_textfile_scrape_error > 0
+ for: 10m
+ labels:
+ alertgroup: "prometheus"
- name: raid
rules:
- alert: raid controller battery failed